Acrel AMC16Z-ZD DC Multi Channel Energy Meter
Acrel AMC16Z-ZD DC Multi Channel Energy Meter
General
AMC16 series products are compact in design, adapt to the characteristics of many load circuits in data centers, realize high integration of monitoring circuits, and can accurately monitor each AC or DC load in the data center. It is suitable for data center server power monitoring and management.
Functions
A+B independent 2 circuits busbar's DC main line
6 passive switching input
2 switching output
1 RS485 communication
Installation:
DIN rail 35mm
Frequency:
Range: 45-65Hz
Dimension (L*W*H):
180*94.3*45mm
Auxiliary Power Supply:
electric signal power supply
Front Panel
①2-channel Switching output
②Second channel current input
③Second channel voltage iuput
④First channel current input
⑤First channel voltage input
⑥RS485
⑦DC12V Power output
⑧Temperature and Humidity Sensor
⑨6-ways passive switching input
Application of AMC16Z-ZD DC Multi Channel Energy Meter
Wiring
Typical Connection
①AMC16Z-FAK24/48 Measure 24/48 channels of each circuit of A+B out line
②AMC16Z-ZA Measure A+B independent 2 circuits three-phase main into line
③RS485 communication line
④AKH-0.66W Type ct or AKH-0.66-EMS type (50,100,200400A)/50mA
⑤AKH-0.66/30I Tpye ct
⑥ATP007kt 7-inch Touch screen or ATP010kt 10-inch Touch screen
On-site Picture
Packaging
Acrel AMC16Z-ZD DC Multi Channel Energy Meter
Product Models
AMC16Z-ZD(-P24)
|
Monitor the full power parameters of the A+B dual DC incoming circuit, monitor the status of 6 switches,
2 alarm outputs, 1 temperature and humidity detection, 1 RS485 communication, ±12V output
(Only power supply to incoming module matching Hall sensor), DC24V independent auxiliary power supply.
|
AMC16Z-FD
|
Monitor the full power parameters of 24 branches of A+B dual-channel DC outlet, and 1 channel of RS485 communication.
|
AMC16Z-FDK24
|
Monitor the full power parameters and switch status of the 24 branches of the A+B dual DC out going line, and 1 channel of RS485 communication.
|
AMC16Z-FDK48
|
Monitor the full power parameters and switch status of the 48 shunts of the A+B dual DC outgoing lines, and 1 channel of RS485 communication.
|
AMC16Z-KA
|
Wet contact, monitoring A+B total 48 branch switch state, 1-way RS485 communication.
|
AMC16Z-KD
|
Dry contact, monitoring A+B total 48 branch switch state, 1-way RS485 communication.
|
AMC16Z-AC220V
|
AC220V extended power supply, and use when the monitoring circuit is beyond 96 branches of A+B
|
Technical Parameters
Technical parameters
|
AMC16Z-ZD(-P24)
|
|
Measurement parameters
|
Voltage, current, power, electrical energy, ambient temperature and humidity
|
|
Bus voltage
|
Rated
|
48VDC,240VDC,336VDC
|
Measuring range
|
±20%
|
|
Overload
|
Instantaneous voltage 2x/sec
|
|
Current incoming loop
|
Rated
|
5V (Hall sensor, powered by AMC16Z-ZD ±12V)
|
Overload
|
Lasts 1.2x, instantaneous 10x/sec
|
|
Temperature and humidity
|
Temperature range
|
-40℃~+99℃
|
Humidity range
|
20%~90%
|
|
Measurement accuracy
|
Incoming wire
|
Voltage/current 0.5 level, power/energy level 1
|
Temperature
|
±1℃
|
|
Humidity
|
±5%
|
|
Auxiliary power supply
|
AMC16Z-ZD: Signal power draw (≤15W).
AMC16Z-ZD-P24: DC24V independent auxiliary power supply
|
|
Environment
|
Temperature
|
Working: -15°C~55°C Storage: -25°C~70°C
|
Humidity
|
Relative humidity ≤ 93%
|
|
Altitude |
≤2500m
|
|
Switching output
|
2CH 3A 250VAC / 3A 30VDC
|
|
Switching input
|
6-way stem node
|
|
Communication
|
RS485/Modbus-RTU
|
|
Installation method
|
DIN35mm rail or baseplate mounting
|
|
Protection level
|
IP20
|
|
Pollution level
|
2 | |
Security
|
Insulation
|
The insulation resistance between all terminals and the conductive parts of the housing is not less than 100MΩ
|
Withstand pressure
|
A voltage and current signal B voltage and current signal switching output between the other ports to meet AC2kV 1min, between the switch input and other ports should be satisfied AC0.5kV 1min, leakage current should be less than 2mA, no breakdown or flash over phenomenon.
|
|
Electromagnetic
compatibility
|
Anti-static
interference
|
Level 4
|
Electrically resistant
fast transient bursts
|
Level 3 | |
Anti-surge
interference
|
Level 4 | |
Resistant to RF
electromagnetic field radiation
|
Level 3 |
1. Manual for Acrel AMC16Z-ZD DC Multi Channel Energy Meter
2. Installation and Use for Acrel AMC16Z-ZD DC Multi Channel Energy Meter
3. Debugging Software for Acrel AMC16Z-ZD DC Multi Channel Energy Meter