Acrel AMC100-ZD DC Precision Power Distribution Monitoring Device
Acrel AMC100-ZD DC Precision Power Distribution Monitoring Device
General
Acrel AMC100 series DC precision power distribution monitor is a measurement device designed specifically for power management of data center servers. The device design exquisite, can for A + B two into line and 192 road for electrical parameters, the input and output parameters of the switch state and the lightning protection device such as real-time monitoring, all alarm threshold measurement channels can be set in A separate, to qualify the limit event trigger system sound and light alarm, immediately on the volume in the traditional instrument, the height of the monitoring circuit integration.
Functions
● Voltage, current, frequency, active power, reactive power, power factor, active energy, reactive energy, , total power parameter measurement
●180mm width
●8DI4DO+1 channel temperature and humidity
●Ethernet (optional)
●3 RS485 channels (2 uplink touch screen and moving ring, 1 downlink sub-module)
Application of AMC100-ZD DC Precision Power Distribution Monitoring Device
Wiring
Typical Connection
①AMC16Z-FAK24/48 Measure 24/48 channels of each circuit of A+B out line
②AMC16Z-ZA Measure A+B independent 2 circuits three-phase main into line
③RS485 communication line
④AKH-0.66W Type ct or AKH-0.66-EMS type (50,100,200400A)/50mA
⑤AKH-0.66/30I Tpye ct
⑥ATP007kt 7-inch Touch screen or ATP010kt 10-inch Touch screen
Matched Current Transformer
AKH-0.66-EMS
AKH-0.66-9N-HB
AKH-0.66-12N-HB
AKH-0.66-20-HB
AKH-0.66-30N-HB
Dimension and Installation
On-site Picture
Packaging
Acrel AMC100-ZD DC Precision power distribution monitoring device
Product Models
AMC100-ZD
|
Monitor the voltage, current, power, and electric energy of 2 independent incoming lines A+B,8 switching input,
4 switching output , 1 temperature and humidity detection, and 3 RS485 communications
|
AMC100-FDK30
|
Monitor the full power parameters and switching status(active) of A+B dual DCoutlet 30 branches,and 1 RS485 communication
|
AMC100-FDK48
|
Monitor the full power parameters and switching status(active) of A+B dual DCoutlet 48 branches, and1 RS485 communication
|
AMC100-FD30
|
Monitor the full power parameters of A+B dual DC outgoing lines in A total of 30 branches, and 1RS485 communication
|
AMC100-FD48
|
Monitor the full power parameters of A+B dual DC outgoing linesin A total of 48 branches, and 1RS485 communication
|
AMC100-KA30
|
Wet contact,monitor the switching status of 30 branches A+B, 1 RS485 communication
|
AMC100-KA48
|
Wet contact,monitor the switching status of 48 branches A+B, 1 RS485 communication
|
AMC100-KD30
|
Dry contact, monitor the switching status of 30 branches A+B, 1 RS485 communication
|
AMC100-KD48
|
Dry contact, monitor the switching status of 48 branches A+B, 1 RS485 communication
|
AMC100-FT30
|
1 wayRS485 communication, 30 way temperature measurement
|
AMC100-FT48
|
1 wayRS485 communication, 48 way temperature measurement
|
Technical Parameters
Technical parameters
|
AMC100-ZD
|
|
Measurement parameters
|
Voltage,Current, Power, Electric energy, Ambient temperature and Humidity
|
|
Bus voltage
|
Rated
|
48VDC,240VDC,336VDC
|
Measuring range
|
±20%
|
|
Overload
|
Instantaneous voltage 2 times/sec
|
|
Current incoming
circuit
|
Rated
|
5V(Hall sensor, ±12V powered by AMC100-ZD)
|
Overload
|
Duration is 1.2 times, instantaneous 10 times/second
|
|
Temperature and
humidity
|
Temperature Range
|
-40℃~+99℃
|
Humidity Range
|
20%~90%
|
|
Measurement
accuracy
|
Coil in
|
Voltage/current level 0.5, power/electric energy level 1
|
Temperature
|
±1℃
|
|
Humidity
|
±5%
|
|
Auxiliary power
|
AMC100-ZD:Signal power(≤15W)
AMC100-ZD-P24:DC 12-24V independent powersupply
AMC100-ZD-P220:
1、When the constant voltage is DC240V、DC336V,powered by AC220V、
DC240V、DC336V independentsupply
2、When the constant voltage is DC48V,powered by DC48V independentsupply
|
|
Environment
|
Temperature
|
Operation:-15℃~55℃ Storage:-25℃~70℃
|
Humidity
|
Relative humidity≤93%
|
|
Altitude
|
≤2500m
|
|
Switch output
|
4-way 3A 250VAC/3A 30VDC
|
|
Switch input
|
8 dry nodes
|
|
Communication
|
1 channel isolatedRS485/Modbus-RTU to the background system
1RS485/Modbus-RTU to touch screen
1RS485/Modbus-RTU connection to the downstream module
1-channel Ethernet communication function is optional
|
|
Installation Method
|
DIN35mm rail or bottom plate installation
|
|
Protection level
|
IP20
|
|
Pollution level
|
2
|
|
Security
|
Insulation
|
The insulation resistance between all terminals and the conductive parts on the shell must be at least 100MΩ
|
Withstand voltage |
Voltage and currentsignal ofline A // Voltage and currentsignal oflineB //
Switching output //Isolated communication port // Two of other ports should meet
AC2kV for 1min,switching input and other ports should meet AC0.5kV for 1min,
leakage current should be less than 2mA, no breakdown or flashover phenomenon.
|
|
Electromagnetic
compatibility
|
Anti-static interference
|
Level 4
|
Reactance fast
transient pulse
|
Level 3
|
|
Surge resistance
|
Level 4
|
|
Radio frequency
electromagnetic
radiation
|
Level 3
|
1. Manual for Acrel AMC100-ZD DC Precision power distribution monitoring device
2. Installation and Use for Acrel AMC100-ZD DC Precision power distribution monitoring device
3. Debugging Software for Acrel AMC100-ZD DC Precision power distribution monitoring device