Acrel AITR Medical isolation transformer

Acrel AITR Medical isolation transformer

● Isolating transformers for medical IT systems
● Double insulation treatment, Electrostatic shielding layer
● PT100 temperature sensor
● Rated power: 3.15…10KVA


Product Detail

Technical Parameters

Certificate

Product Tags

Acrel AITR Medical isolation transformer

General

Acrel AITR series isolation transformer is specially used in medical IT system. The transformer core is made of silicon steel sheet, the loss is small. Double insulation treatment is adopted between windings, and a static screen is designed to reduce the electromagnetic interference between the two windings. PT100 temperature sensor is installed in the winding, which can be used to monitor the winding temperature. The transformer is treated by vacuum impregnation, which increases the mechanical strength and has anti-corrosion effect. In addition, the product also uses low temperature rise and low noise design, so that it has good temperature rise performance and low noise.

Typical Connection

AID150 - connection - 1

Outline and Dimension

AITR medical isolation transformer - dimension
AITR medical isolation transformer - dimension - 2

Advantages of Hospital Isolated Power System

Medical isolated power panels provide safe, reliable and continuous power distribution for the important equipment at these locations:

• Used for the transformation of TN system into IT system (ungrounded system)

• Functions of real-time monitoring and fault alarming of the ground insulation resistance, transformer load current and transformer winding temperature of the monitored IT system

• When the monitored IT system has an insulation fault, the hospital isolation panel can initiate and generate the fault location signal to the system, and realize fault locating function with the help of the fault locator

• Acrel hospital isolated power systems can remotely monitor the real-time operating conditions of up to 16 pieces of systems, and the main interface intuitively displays whether the access system communication is intact

Acrel Medica/Hospital Isolated Power Systems FAQs

What is hospital isolated power system?

It is an isolated power supply system that conducts insulation monitoring and fault determination of the power distribution system, to further provide safe, reliable and continuous power distribution.

What are functions of medical isolated power panels?

Real-time monitoring of the insulation, load and isolation transformer temperature of the IT system, with functions such as system insulation fault circuit location and centralized monitoring of multiple systems.

What's the consists of medical isolated power supply system?

The medical isolated power supply system consists of a medical isolation transformer, medical intelligent insulation monitoring instrument, current transformer, insulation fault locator, test signal generator, power module and centralized alarm and display instrument.

What are the applications of hospital isolated power systems?

You can find medical isolation panels in operating rooms, ICU/CCU intensive care units, premature infant care units, delivery rooms, hemodialysis centres, emergency rooms and other important medical places.


  • Previous:
  • Next:

  • Acrel AITR Medical isolation transformer

    Technical Parameters

    Type AITR10000 AITR8000 AITR6300 AITR5000 AITR3150
    Insulation class H H H H H
    Protection class IP00 IP00 IP00 IP00 IP00
    Power/voltage/ current
    Rated power 10000VA 8000VA 6300VA 5000VA 3150VA
    Rated frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz
    Rated input voltage AC230V AC230V AC230V AC230V AC230V
    Rated input current 45.3A 36A 28.5A 22.5 14.2A
    Rated output voltage AC230V/115V AC230V/115V AC230V/115V AC230V/115V AC230V/115V
    Rated output current 43.5A 34.7A 27.4A 21.7A 13.7A
    Inrush current <12In <12In <12In <12In <12In
    Leakage current <200μA <200μA <200μA <200μA <200μA
    No load input current 1.359A 1.08A 0.855A 0.675A 0.426A
    No load output voltage 235V±3% 235V±3% 235V±3% 235V±3% 235V±3%
    Short circuit voltage <6.9V <6.9V <6.9V <6.9V <7.5V
    General parameters
    Fuse wire 80A 63A 50A 35A 25A
    Primary winding resistance <55mΩ <64mΩ <80mΩ <131 mΩ <245mΩ
    Secondary winding resistance <45mΩ <64mΩ <80mΩ <116 mΩ <228mΩ
    Iron loss <150W <105W <107W <77W <55W
    Copper loss <230W <200W <170W <125W <125W
    Efficiency >96% >96% >96% >96% >96%
    Maximum ambient temperature <40℃ <40℃ <40℃ <40℃ <40℃
    No-load temperature rise <36℃ <33℃ <31℃ <26℃ <22℃
    Full load temperature rise <65℃ <76℃ <67℃ <62℃ <55℃
    Noise grade <40dB <40dB <40dB <40dB <40dB

    AITR S Series Isolation Transformer CE Certificate