ACREL AC Energy Meter’s Application in PV System in Bulgaria

Background

This paper introduces the application of Acrel APM series AC meter in the AC side of the Bulgarian photovoltaic system. It is mainly used to measure the current in the photovoltaic system, and cooperate with the transformers to measure, communicate and control the circuit system.

Project Overview

The company is located in Bulgaria. The company is mainly engaged in the design/installation, construction/maintenance of small photovoltaic power generation center projects in Bulgaria and surrounding countries. The customer wants to use AC meters apm801, apm810 and mutual inductors for monitoring, metering and communication of current and voltage at the AC side of the photovoltaic system, and control by using the switching value function of the APM meter.

APM Series Energy Meters

Acrel power meter is designed according to IEC standards and synchronized with international advanced technology.

APM series meters have full power measurement, energy statistics, analysis of power quality and network communications and other functions. This multi-function digital meter series is mainly used for comprehensive monitoring of the quality of power supply network.

This series of meters use a modular design, with a rich function of the external DI / DO module, AI / AO module, event recording (SOE) module with T-Flash (TF) card, network communication module, Temperature and humidity measurement module, can achieve full power measurement of an electrical circuit and monitoring of switch status, Dual RS485 with Ethernet interface can realize data copying of RS485 master station, eliminating the need for data switching exchange. PROFIBUS-DP interface can realize high-speed data transmission and networking functions.

Type and Function Description

Function APM800(class 0.5s) APM801(class 0.2s) APM810(class 0.5s)
Measured parameters Total electrical measurement
Four-quadrant energy
The pulse output of energy The pulse output of active/reactive energy
Demand Three-phase current, active power, reactive power, real-time demand of apparent power, and maximum demand (including the timestamp)
Extreme value statistics Extreme of current, line voltage, phase voltage, active power, reactive power, apparent power, power factor, frequency, total harmonic of current, total harmonic of voltage in this month and last month (including the timestamp)
Power quality Unbalance of current, line voltage, phase voltage
Voltage phase angle, current phase angle
Voltage current phase Angle
Total (odd, even) harmonic content of voltage and current × ×
The harmonic content of voltage and current (2-63 times)① × ×
Voltage crest factor × ×
Telephone waveform factor × ×
Current K-factor × ×
Alarm records A total of 66 kinds of alarm types, each type can record the most recent 16 alarm records, support extended records by TF card
Event log Record the most recent 128 event records, support extended records by TF card
 Communication Modbus protocol
I/O 2 digital inputs + 2 digital outputs (2DI+2DO)
Extensions MD82 8 digital inputs + 2 digital outputs with changeover contacts (8DI+2DO)
MLOG TF card storage (alarm records, event records, electrical parameters and energy timing records, etc.)
MA84 8 analog inputs (class 0.5) + 4 analog outputs (class 0.5) (8AI+4AO)
MCM  1 RS485/Modbus-RTU, support master mode or slave mode
MCP 1 Profibus-DP
MCE 1 Ethernet, support Modbus-TCP, HTTP, SMTP, DHCP protocol
MTH 4 ways of temperature measurement, 1 way of temperature and humidity control

Technical parameters

 

Technical Parameters Index 
Signal Electrical network Three-phase three-wire, three-phase four-wire, see the wiring diagram;
Frequency 45~65Hz;
Voltage Rated value: AC 100V、110V、400V、690V;
Overload: 1.2 times rated value(continuous); 2 times rated value /1 second;
Power consumption: < 0.5VA (per channel);
Current Rated value: AC 1A, 5A, support 4 mm2 line access;
Overload: 1.2 times rated value(continuous); 10 times rated value/1 second;
Power consumption: < 0.5VA (per channel);
Measurement accuracy Voltage、current and power class 0.5s/class 0.2s (APM800、APM810/APM801)
Active power class 0.5s/class 0.2s (APM800、APM810/APM801)
Reactive power class 2
Harmonic 1%(2rd~42nd)、2%(43rd~63rd)
Switch inputs Dry contact inputs, built-in power supply;
Relay outputs Contact type: open contact in the main part, changeover contact in the module;Contact capacity: AC 250V/3A  DC 30V/3A;
The pulse output of energy Output mode: Optocoupler pulse with open collector;Pulse constant:4000(5A)、8000(1A) imp/kWh;
Analog outputs DC 0mA~20mA、4mA~20mA、0V~5V、1V~5V output, accuracy class 0.5%, load resistance ≤ 500Ω;
Analog inputs DC 0mA~20mA、4mA~20mA、0V~5V、1V~5V iutput, accuracy class 0.5%
Storage card Standard Capacity:4G, TF Card Up to 32G Capacity;
Communication RS485 interface/Modbus-RTU protocol and DLT645 protocolProfibus-DP interface/Profibus-DP protocol;

RJ45 interface (Ethernet) / Modbus-TCP, HTTP, DHCP and other protocols;

Power supply Working range: AC/DC 85V~265V or AC/DC 115~415V(P2);Power consumption: Power consumption of the main part ≤ 15VA;
Safety Power frequency withstand voltage The power frequency withstand voltage between the shell and the auxiliary power supply, each input and output terminal group is AC 4kV/1min;The power frequency withstand voltage between the auxiliary power supply and each input and each output terminal group is AC 2kV/1min;

The power frequency withstand voltage between the voltage input and other input/output terminal groups are AC 2kV/1min;

The power frequency withstand voltage between the current input and other input/output terminal groups are AC 2kV/1min;

The power frequency withstand voltage between the relay output and other input/output terminal groups are AC 2kV/1min;

The power frequency withstand voltage between each terminal group of switch input, communication, analog output and pulse output is AC 1kV/1min;

Insulation resistance Inputs、outputs to the shell>100MΩ;
Electromagnetic compatibility Meet IEC 61000 standard (Level 4);
Protection level Display panel IP52
Environment Operating temperature: -20 °C ~ +65 °C;Storage temperature: -20°C~+70°C;

Relative humidity: ≤95% without condensation;

Altitude: ≤2500m;

Standards IEC 60068-2-1IEC 60068-2-2

IEC 60068-2-30

Environmental Testing-Part 2-1:Tests Test A:Cold IDAPart 2-1:Tests Test B:Dry heat

Part 2-30:Tests Test Db:Damp heat,cyclic(12+12h)

IEC 61000-4 Electromagnetic compatibility-Testing and measurement techniques
IEC 61557-12 Electrical safety in low voltage distribution system up to 1000V a.c. and1500V d.c –Equipment for testing,measuring or monitoring of protective measures- Part12:Performances measuring and monitoring devices(PMD)
IEC 62053-22 Electricity metering equipment (a.c.)-Particular requirements - Part22:Static meter for active energy(class 0.2s and 0.5s)

Requirements from Customer

terms of reference from grid supplier:

(1)monitoring voltages: L1-N, L2-N, L3-N. Unominal = 230V;

(2)switching relay output at overvoltage: 2 steps:

Step 1: 110% of Unominal or 253V - delay 60 seconds (s) ;

Step 2: 115% of Unominal or 264V - delay 0.1s;

(3)switching relay output at Undervoltage:

1-step; 80% of Unominal or 184V - delay 0.2s; Range of settings: U: 10-100% of Unominal, step not listed, maybe 1V to 1%; Delay: 0.05 s to 3s, step - not listed, maybe 1s;

(4)switching relay output at over frequency

1-step; 50.5Hz - delay 0.1s; Range of settings: F: 50-52.5Hz, step 0.1Hz; Delay: 0.1-0.5s, step - maybe 0.1s;

(5)switching relay output at over frequency

1- step; 47.5Hz - delay 0.1s; Range of settings: F: 47.5-50Hz, step 0.1Hz; Delay: 0.1-0.5s, step - maybe 0.1s;

(6)Delay for recovering. When DO is on by some of the previous reasons, there should be a time delay after grid parameter(s) are back in nominal range(s). Time range 1-60s, step 1s

(7)Additional settings. (If they are possible).

7.1 When Unominal is lower than 60-70%, under and over frequency monitoring can be disabled

7.2 When over frequency/under frequency is happened - the DO should not be recovered automatically, it should wait for some kind of manual/remote restore.

The above 7 items are the special needs of customers for the purchased products. Except that some requirements in point 7 cannot meet the needs of customers, other needs can be met. Basically solved the needs of customers.